Assemblies like this are often found in riser rooms.
Fire sprinkler riser room signage requirements.
7 inches high by 10 inches width with 0 5 inch letter stroke white reflective letters on a red background and shall be permanently attached at normal eye level to the door leading to the fire sprinkler control equipment.
The requirement all sprinkler systems are required to provide a general information sign placed at each system control riser antifreeze loop and auxiliary system control valve.
Access doors for automatic sprinkler system riser rooms and fire pump rooms shall be labeled with an approved sign.
Signage is required on the access doors to fire pump and riser rooms and shall consist of letters at least two inches in height.
Permanent artificial lighting is now required to be installed by the 2018 ifc ibc.
Fire department sprinkler signs pipe markers and nfpa signs for your facility s fire safety plan.
Sprinkler riser room signs are intended to alert emergency response and maintenance crews to the location of fire sprinkler system risers.
Quickly identify critical fire riser rooms when you need them the most.
Permanently installed artificial illumination shall be provided in the automatic sprinkler system riser rooms and fire pump rooms.
Use vivid labels or signs to equip multiple fire protection systems.
Fast shipping direct from usa manufacturer.
There shall be 36 inches of clearance in front of the fire alarm control panel facp.
Risers are the vertical supply pipes in sprinkler systems as defined by nfpa 13 sec.
Help personnel and emergency responders easily locate your sprinkler system controls.
Automatic sprinkler system riser rooms and fire pump rooms shall be maintained at a temperature of not less than 40ºf 4ºc.
For instance the town of brighton n y stipulates the following for fire sprinkler riser room signage.
Fire pump and riser rooms shall be maintained to be no lower than 40 degrees fahrenheit with the heating device permanently installed.
One side may be a minimum of 18 inches from a wall.
The minimum size of the equipment room shall allow adequate firefighter access and mobility with the following minimum clearance requirements.
The letterings hall be in contrasting color to the background.
Fire sprinkler pipe markers.
Fire riser room signs.
Most fire sprinkler system valves must be identified with metal or rigid plastic signs section 6 6 4 of nfpa 13 stipulates sign requirements for all control drain venting and test connection valves while section 8 16 1 1 expands on the guidance for control valves.
Use indoors or outdoors to provide superior resistance to weather.
Riser assembly shall have a minimum of 36 inches of clearance around the pipe.
Mount on doors or hang from riser systems with a chain.